Unit 2A, Axis Business Park, Tullamore, Co Offaly
24 HOUR CALLOUT 057 93 61004

Series 65 Heat Detector

25.00 ex VAT

The Series 65 Heat Detectors monitor temperature by using either a dual thermistor network or a single thermistor network (CS versions), providing a voltage output proportional to the external air temperature.

Category:

Description

Key Features

  • Ideal for environments that are dirty or smoky under normal circumstances
  • Suitable where smoke detectors are unsuitable
  • Wide operating voltage: 9 V to 33 V DC

Product Information

Supply wiring Two-wire monitored supply, polarity insensitive
Terminal functions L1 IN & L2 IN; L1 OUT & L2 OUT; –R remote indicator negative connection
Supply voltage 9 V to 33 V DC
Ripple voltage 2 V peak-to-peak max at 0.1 Hz to 100 kHz
Alarm voltage 6 V to 28 V DC
Alarm indicator Red light emitting diode
Design alarm load 420 Ω in series with a 2 V drop
Holding voltage / current 6 V / 10 mA
Remote output (–R) Current sink to negative line, limited to 17 mA
Storage temperature –30 °C to +80 °C
Operating temperature A1R: –20 °C to +50 °C;
BR: –20 °C to +65 °C;
CS/CR: –20 °C to +80 °C
Humidity 0 % to 95 % RH (no condensation or icing)
IP rating IP54
Dimensions Ø 100 mm × H 42 mm
Weight 80 g
Materials Housing: white flame-retardant polycarbonate; Terminals: nickel-plated stainless steel

Current Characteristics

Supply Voltage (V) Quiescent (A1R Std) Alarm (A1R Std) Quiescent (A1R LED) Alarm (A1R LED) Quiescent (A1R LED/Mag) Alarm (A1R LED/Mag)
24 45 µA 52 mA 55 µA 52 mA 55 µA 52 mA
9 40 µA 17 mA 50 µA 17 mA 50 µA 17 mA

Variants & Part Numbers

Class Max Application Temp (°C) Max Static Response Temp (°C) Part No. Standard Part No. Flashing LED
A1R 50 65 55000-122 55000-121
BR 65 85 55000-127 55000-126
CR 80 100 55000-132 55000-131
CS 80 100 55000-137 55000-136

Operation

In the A1R, BR and CR variants, paired NTC thermistors (one exposed, one insulated) sit on the PCB. Under stable conditions they have equal resistance; a rapid temperature rise causes the exposed thermistor’s resistance to drop relative to the insulated one. When the ratio exceeds a factory preset threshold, the detector alarms. CS variants use a single NTC thermistor network to provide a voltage output proportional to ambient temperature.

Compliance & Certification

  • EMC Directive 2014/30/EU
  • Construction Products Regulation (EU) 305/2011
  • CPR, LPCB, VdS, VNIIPO, SBSC, FG & BOMBA approvals*
  • ISO 9001:2015 & ISO 14001:2015 certified (LPCB ref. 010)

*Not all detectors carry every approval; see product pages for details.